User Requirements Specification (URS) for the Cleanrooms

23/03/2025by admin0
URS_Cleanrooms-1280x853.webp

A User Requirement Specification (URS) is a critical document for designing, constructing, and validating a cleanroom. It outlines the specific requirements and expectations for the cleanroom’s operation, functionality, and compliance with industry standards. Below is a comprehensive outline for Cleanroom URS:

1. Introduction

Purpose:

The cleanroom is designed to provide a controlled environment where airborne particles, microbial contamination, and other contaminants are minimized, making it suitable for highly sensitive operations. The cleanroom is intended for use in the following sectors:

  • Pharmaceutical Manufacturing: To ensure the production of pharmaceutical products such as injectable drugs, vaccines, and other critical medical therapies in a sterile and contamination-free environment.
  • Biotechnology Research: To conduct experiments and research involving biological materials that require a controlled environment to ensure the safety, accuracy, and reliability of research results.
  • Medical Device Production: To manufacture and assemble medical devices that meet strict cleanliness and sterility standards to ensure patient safety and product effectiveness.

The cleanroom will maintain the environmental conditions necessary for producing, testing, or handling sensitive products where contamination could compromise quality and safety.

Scope:

This cleanroom project encompasses the design, construction, and operational systems necessary to meet the regulatory and client-specific requirements for maintaining a controlled environment. The key components within the scope of this project include:

  • HVAC Systems: Proper airflow, filtration, and environmental control mechanisms, including temperature, humidity, and air pressure control systems, to ensure optimal conditions are always maintained.
  • Electrical Systems: Adequate power supply for cleanroom operations, including emergency backup power systems (such as UPS) to ensure continuous functionality of critical systems during power outages.
  • Monitoring Systems: Install systems for environmental monitoring (temperature, humidity, particle counts, etc.) and real-time data logging, including alarms and alerts for deviations outside acceptable limits.
  • Air Filtration: HEPA or ULPA filters will reduce particulate matter to an acceptable level based on the cleanroom classification (e.g., ISO Class 7, Class 8).
  • Personnel and Materials Flow: Implement gowning areas, airlocks, and procedures to control personnel and material movement into and out of the cleanroom.

Areas or systems not directly related to the cleanroom environment, such as office spaces, general facility infrastructure, or non-GMP-compliant areas, may be excluded from this project scope.

Background:

The cleanroom is being developed according to current regulatory requirements such as the ISO 14644-1 standard for cleanroom classification, Good Manufacturing Practices (GMP), and any local regulations from regulatory bodies like the FDA or Health Canada. The facility must comply with the specific environmental conditions mandated for the cleanroom’s intended use, such as sterile drug production, research activities, or medical device manufacturing.

Specific client or industry requirements will also shape the cleanroom design, including any unique processes, certifications (e.g., ISO 13485 for medical devices), and validation protocols (such as IQ/OQ/PQ). Additionally, if the cleanroom is intended for FDA-regulated operations, it must be designed to meet 21 CFR Part 211 for pharmaceutical manufacturing.

The cleanroom’s construction and operation will prioritize compliance with national and international standards and the industry’s best practices to ensure the highest quality and safety of products produced in this environment.

Cleanrooms | Cleanroom Consulting | Biotech Cleanrooms

 

2. Regulatory and Standards Compliance

ISO Standards:

The cleanroom must be classified according to ISO 14644-1 to meet the necessary cleanliness requirements based on the intended use. The classification is determined by the concentration of airborne particulate matter, which particle counts per cubic meter measure. The cleanroom classification should align with the requirements of the specific industry and processes involved.

  • ISO 14644-1 Classifications:
    • ISO Class 5: Suitable for the most sensitive applications, such as sterile pharmaceutical manufacturing, where contamination levels must be extremely low (particles greater than 0.5 microns should be limited to 3,520 per cubic meter).
    • ISO Class 7: Used for applications like biotechnology research, where a low particle count is necessary, but slightly higher contamination levels may be acceptable (particles greater than 0.5 microns should be limited to 352,000 per cubic meter).
    • ISO Class 8: Generally used for less sensitive processes, such as assembly of medical devices (particles greater than 0.5 microns should be limited to 3,520,000 per cubic meter).

The exact class will depend on the operation’s specific needs. The cleanroom should be designed and validated to meet the required ISO classification as per ISO 14644-1. The classification must be verified during the cleanroom’s commissioning and requalification.

FDA or Health Canada Requirements:

For cleanrooms used in regulated environments such as pharmaceutical manufacturing or medical device production, compliance with regulations from health authorities like the FDA (U.S. Food and Drug Administration) or Health Canada is essential.

  • FDA Requirements:
    • 21 CFR Part 211: This part of the FDA regulations outlines the current Good Manufacturing Practices (cGMP) for pharmaceuticals. Cleanrooms used in pharmaceutical manufacturing must meet the conditions specified in 21 CFR Part 211, which includes requirements for sanitation, cleanliness, and the maintenance of proper environmental controls in manufacturing areas.
    • FDA 21 CFR Part 820: If the cleanroom is used for medical device manufacturing, it must comply with 21 CFR Part 820—the regulations for quality management systems in medical device manufacturing. This includes requirements for cleanroom environment controls to ensure device sterility and integrity.
  • Health Canada Requirements:
    • Health Canada’s Food and Drug Act (FDA) and Regulations: Health Canada regulates pharmaceutical manufacturing in Canada and enforces GMP standards that mirror those of the FDA. Cleanrooms used for pharmaceutical manufacturing in Canada must adhere to the Canadian GMP guidelines harmonized with international GMP requirements.
    • Health Canada’s Guidance on Cleanrooms and Environmental Controls: These guidelines provide details about the minimum requirements for cleanrooms, including the types of cleanroom classes and environmental control specifications for operations under Health Canada’s purview.

Compliance with these regulatory requirements is necessary to ensure that the cleanroom environment supports the safe and effective production of pharmaceutical and medical products. Documenting the procedures, controls, and qualification activities required to comply with these regulations is also essential.

Other Relevant Standards:

In addition to ISO and regulatory requirements, other standards may apply to the cleanroom design and operations, depending on the specific application and industry needs. Some of these include:

  • Good Manufacturing Practice (GMP):
    • Cleanrooms used in pharmaceutical manufacturing, biotechnology, and medical device production must meet GMP requirements, which cover areas such as personnel hygiene, equipment maintenance, facility cleanliness, and environmental monitoring.
    • EU GMP (Annex 1): If a cleanroom is intended for use in a European market, the design must comply with EU GMP Annex 1. This Annex focuses on manufacturing sterile medicinal products and outlines requirements for cleanroom classifications, air changes, filtration, and other environmental controls.
    • cGMP: In the United States, cleanrooms must adhere to current Good Manufacturing Practices (cGMP), which include strict guidelines on contamination control, environmental monitoring, and maintenance.
  • International Council for Harmonization (ICH) Guidelines:
    • ICH Q7: The ICH Q7 guidelines for Good Manufacturing Practices for Active Pharmaceutical Ingredients may apply to cleanrooms that produce active pharmaceutical ingredients (APIs). These guidelines set expectations for facility design, cleanliness, and operations in producing high-quality pharmaceuticals.
    • ICH Q9: For risk management within the cleanroom environment, ICH Q9 provides guidelines on quality risk management practices that can be applied to ensure product quality and safety in cleanroom operations.
  • ISO 13485: If the cleanroom is being used to manufacture medical devices, it must comply with ISO 13485, which outlines the quality management system requirements for medical devices. This standard ensures that the cleanroom’s design and operation meet the device safety and efficacy regulatory requirements.
  • ISO 14698: For microbial control, ISO 14698 outlines the requirements for monitoring and controlling microbial contamination in cleanrooms, which is essential for environments involved in pharmaceutical production and biotechnology applications

Biologics Manufacturing I Cleanroom Design Qualification Process

3. Cleanroom Classification and Environmental Control

Cleanroom Classification:

The cleanroom should be classified according to ISO 14644-1, which defines the cleanliness level based on particle concentration. The classification should be based on the application’s specific needs and industry.

  • ISO 14644-1 Classifications:
    • ISO Class 5: Suitable for highly sensitive operations such as sterile drug manufacturing or research where contamination must be extremely low (particles greater than 0.5 microns should be limited to no more than 3,520 particles per cubic meter).
    • ISO Class 7: Appropriate for less sensitive operations like biotechnology research or specific medical device production, where contamination limits are slightly higher (particles greater than 0.5 microns limited to 352,000 particles per cubic meter).
    • ISO Class 8: Suitable for lower-level sensitivity applications requiring contamination control, such as assembly or packaging of medical devices (particles greater than 0.5 microns limited to 3,520,000 particles per cubic meter).

The chosen cleanroom classification should meet the operational requirements and regulatory standards of the industry in which it will be used.

Airborne Contaminants:

  • Particulate Contamination Limits:
    • The maximum allowable particle concentration (per cubic meter) should be specified for each ISO cleanroom class, based on particle size, typically 0.5 microns. For example:
      • ISO Class 5: No more than 3,520 particles per cubic meter of air (≥0.5 microns).
      • ISO Class 7: No more than 352,000 particles per cubic meter of air (≥0.5 microns).
      • ISO Class 8: No more than 3,520,000 particles per cubic meter of air (≥0.5 microns).
    • Particle counters and other monitoring systems should be installed to continuously monitor particle concentration levels to ensure they stay within acceptable limits.
  • Chemical Contamination Limits:
    • If applicable, the cleanroom may need to be monitored for specific chemical contaminants (e.g., volatile organic compounds, solvents, or gases).
    • The acceptable levels of chemical contaminants will depend on the materials being processed. For example, pharmaceutical manufacturing might require monitoring of residual solvents, while biotechnology research might require monitoring for specific reagents or biomolecules.
  • Microbial Contamination Limits:
    • Microcontamination limits must be specified for sterile environments (e.g., pharmaceutical or medical device manufacturing). Microbial limits could be expressed as:
      • Microbial counts: Maximum allowable CFU (colony-forming units) per cubic meter of air.
      • Environmental sampling: Regular microbial sampling of surfaces or air should be conducted, and acceptable limits for microbial contamination must be defined (e.g., 0 CFU for a sterile environment or controlled levels for non-sterile environments).
    • Depending on the class and process needs, airborne microbial contamination may also be controlled using UV sterilization or HEPA filtration.
  • Other Contaminants:
    • For cleanrooms that handle sensitive equipment, components, or research, other environmental contaminants, such as particulates from workers, equipment, or materials, may need to be considered. If necessary, specific limits can be set for these contaminants.

Temperature, Humidity, and Pressure Control:

  • Temperature:
    • The cleanroom’s temperature must be maintained within a narrow range to ensure proper manufacturing processes or research conditions.
      • Example: Temperature maintained between 18–24°C.
    • Temperature sensors should be placed throughout the cleanroom to monitor and record environmental conditions. The system should have alarms if the temperature falls outside acceptable ranges.
  • Humidity:
    • Humidity control prevents static electricity buildup, product degradation, and other process issues.
      • Example: Maintain relative humidity between 30% and 60%.
    • Humidity should be monitored using humidity sensors. Humidity levels must be within the required range to prevent any potential impact on the cleanroom processes.
  • Pressure Control:
    • Differential air pressure between rooms should be controlled to prevent contamination from entering the cleanroom from lower-class areas (or outside).
      • Example: Maintain a minimum 10 Pa differential pressure between the cleanroom and adjacent areas to prevent particle and contamination ingress.
    • The pressure difference between the cleanroom and adjacent areas must be continuously monitored and recorded.
    • Positive Pressure is commonly used to keep particulate-laden air from entering the cleanroom, especially in sterile environments (e.g., pharmaceutical manufacturing or surgical equipment production).

Airflow and Ventilation:

  • Airflow System Requirements:
    • The cleanroom must have an HVAC system (Heating, Ventilation, and Air Conditioning) that meets the airflow requirements to maintain cleanliness levels.
    • The system must be designed to provide the required air changes per hour (ACH). Typical requirements may be:
      • ISO Class 5: Minimum of 240–500 air changes per hour (ACH).
      • ISO Class 7: Minimum of 30–60 ACH.
      • ISO Class 8: Minimum of 20–40 ACH.
    • The cleanroom should be equipped with HEPA or ULPA filters to ensure efficient filtration of airborne particles.
      • HEPA filters typically have an efficiency of 99.97% for particles ≥0.3 microns, and ULPA filters provide even higher filtration efficiency, up to 99.999%.
  • Laminar Flow:
    • For higher-class cleanrooms (e.g., ISO Class 5), laminar flow is required to provide unidirectional airflow that directs particles away from critical areas. Laminar flow can be provided through horizontal or vertical laminar flow hoods or systems built into the cleanroom structure.
    • Laminar flow ensures that air moves in a single direction with a constant velocity, reducing turbulence and particle disturbance.
  • Unidirectional Airflow:
    • In some cases, the cleanroom may require unidirectional airflow to prevent contamination during sensitive processes, such as producing sterile products or assembling clean equipment.
    • Unidirectional airflow requires installing a specialized system that directs air consistently and is controlled to reduce cross-contamination risks.
    • This is particularly necessary for aseptic processing, sterile packaging, or operations involving highly sensitive biotech materials.
  • Air Recirculation and Filtration:
    • The HVAC system should be designed to allow sufficient air recirculation within the cleanroom while filtering contaminants.
    • Recirculation must be done through HEPA/ULPA filters, ensuring that any recirculated air remains free from particulate and microbial contamination

4. Cleanroom Design

Room Layout:

  • Entry and Exit Points:
    • The cleanroom should be designed with clearly defined entry and exit points to prevent contamination from entering the controlled environment.
    • Main Entry: Should be in a designated area with access controls, including security measures to restrict unauthorized entry.
    • Exit Routes: Separate exit pathways for personnel and materials should be specified to minimize the risk of contamination. Ensure that the exit flows away from clean and sterile zones.
  • Gowning Areas:
    • Gowning Area: Located at the cleanroom entry, the gowning area should be designed for proper gowning and de-gowning procedures. It should be equipped with necessary amenities, such as:
      • Changing stations: This is for personnel to wear protective clothing (gowns, gloves, shoe covers, etc.).
      • Air showers: To remove any potential particulate matter from personnel before entering the cleanroom.
      • Storage for protective equipment: Shelves, hooks, or lockers for storing personal belongings and cleanroom garments.
    • Gowning procedures: Clear instructions for personnel on the required gowning steps to ensure cleanliness before entering the cleanroom.
  • Airlocks:
    • Airlocks are essential to minimize contamination risks between different cleanroom zones. Airlocks should be designed with:
      • Positive Pressure: When doors are opened, positive pressure ensures that clean air flows from the cleanroom to the less-clean areas.
      • Two-Door System: This system maintains the pressure difference by ensuring one door is always closed before the other opens.
      • Hand washing stations and sanitizers should be provided within air locks as additional hygiene control before entering or exiting.
  • Storage Areas:
    • Material Storage: Clean, sterile materials should be stored in designated areas within the cleanroom. Storage areas should be separated into clean zones for sterile materials and dirty zones for non-sterile materials.
    • Equipment Storage: Equipment should be stored in a way that minimizes contamination risks and is easy to clean. Shelves or cabinets should be smooth and easy to wipe down.
    • Waste Disposal: Designated waste disposal areas should be provided to safely dispose of used materials (e.g., gloves, garments, packaging waste).
  • Zones Based on Cleanliness Requirements:
    • Sterile Zone: Areas where sterilized or highly sensitive products are handled, such as sterile pharmaceutical production or aseptic filling. This zone will require the highest level of contamination control (ISO Class 5 or similar).
    • Clean Zone: Less stringent than sterile zones, clean zones are used for processes that do not involve sterile handling but still require contamination control (e.g., equipment assembly). They are typically classified as ISO Class 7 or 8.
    • Dirty Zone: Entry points for materials, equipment, or personnel that have not been decontaminated or have a lower cleanliness requirement. This zone will not require the same high-level air filtration or contamination controls as the clean or sterile zones.

Cleanroom Certifications I Cleanroom CQV | Cleanrooms

Materials and Construction:

  • Materials for Construction:
    • To minimize the risk of contamination, all surfaces in the cleanroom should be smooth, non-porous, and easy to clean.
      • Walls: Using epoxy-coated or stainless-steel surfaces for non-porous walls resistant to damage or contamination.
      • Floors: Non-slip, seamless, and smooth epoxy-coated floors are ideal for cleanrooms, as they are easy to clean and maintain. Floor joints should be sealed to prevent the buildup of dirt and particles.
      • Ceilings: Ceiling panels should be made of smooth, non-porous materials that are easy to wipe down and maintain. Raised ceilings may be used to accommodate HVAC systems and provide better airflow.
      • Windows and Doors: Use non-porous, easy-to-clean materials like laminated glass or polycarbonate for windows. Doors should be airtight and equipped with appropriate sealing mechanisms.
  • Design Features to Prevent Contamination:
    • Corner Construction: Use radiused corners (curved edges) on walls, ceilings, and floors to prevent dirt accumulation, essential for maintaining cleanliness.
    • Sealing: Ensure all joints between walls, floors, and ceilings are correctly sealed to prevent particle buildup and facilitate easy cleaning.
    • Cleanroom Doors: Install easy-to-clean, ideally automatic, self-closing doors to reduce the need for personnel to touch them and minimize contamination risks physically.
  • Durability and Maintenance:
    • All materials used should be durable enough to withstand the cleaning procedures, including chemical cleaning agents. The design should include easy-to-access areas for cleaning and maintenance without compromising the integrity of the cleanroom environment.

Personnel Access:

  • Access Control Systems:
    • Gowning and De-Gowning Procedures: Personnel must follow strict gowning and de-gowning procedures, which include using cleanroom-specific protective garments such as gowns, gloves, shoe covers, and face masks. The gowning area should have instructions and proper equipment to facilitate these processes.
    • Airlocks: Implement airlocks at the cleanroom’s entry and exit points, where personnel must pass through to decontaminate or prevent contamination.
    • Positive Pressure: The cleanroom should maintain positive pressure concerning adjacent rooms to prevent the flow of contaminants into the cleanroom when doors are opened.
  • Personnel Flow:
    • Clear procedures for personnel flow should be established to minimize cross-contamination. These procedures should ensure that personnel do not move from a higher-class area to a lower-class area without proper decontamination.
    • Zoning for Personnel Movement: To minimize cross-contamination, personnel should move from dirty zones (e.g., locker rooms, break areas) to clean and sterile zones following a controlled, sequential flow.
    • Separation of Activities: To reduce the impact on cleanliness, separate cleaning and maintenance staff from those directly handling sensitive products and ensure that maintenance is scheduled during non-operational hours.
  • Access Control and Monitoring:
    • Electronic Access Control systems (e.g., swipe cards, biometrics) should limit access to specific cleanroom zones based on roles and responsibilities. Only authorized personnel should be allowed in the cleanroom.
    • Personnel Monitoring: Wearable systems or badge readers may be used to track personnel movements and ensure proper procedures are followed.

5. Equipment and Utilities

HVAC System:

The Heating, Ventilation, and Air Conditioning (HVAC) system is a critical component of cleanroom design. It must maintain a consistent and controlled environment for the cleanroom processes and ensure proper air quality, temperature, humidity control, and particle removal.

  • Airflow Requirements:
    • Air Changes per Hour (ACH): The HVAC system must provide the required air changes per hour (ACH) to ensure the desired cleanliness level. For example:
      • ISO Class 5: Typically requires 240 to 500 ACH.
      • ISO Class 7: Typically requires 30 to 60 ACH.
      • ISO Class 8: Typically requires 20 to 40 ACH.
    • Unidirectional Airflow: For higher-class cleanrooms (e.g., ISO Class 5), the system must provide laminar or unidirectional airflow to reduce turbulence and ensure continuous air movement away from sensitive areas.
    • Positive Pressure: Maintain positive pressure within the cleanroom to prevent particles from ingressing from adjacent areas. The pressure differential between the cleanroom and adjacent rooms should typically be at least 10 Pa.
  • Filtration:
    • HEPA or ULPA Filtration: The system must have High-Efficiency Particle Air (HEPA) filters for ISO Class 7 or 8 cleanrooms, and ultra-low penetration air (ULPA) filters for ISO Class 5 or highly sensitive areas.
      • HEPA filters should have a filtration efficiency of 99.97% for particles ≥0.3 microns.
      • ULPA filters offer even greater efficiency (99.999% for particles ≥0.12 microns).
    • Pre-Filters: In addition to HEPA/ULPA filters, pre-filters must be installed to capture larger particles and extend the life of primary filters.
  • Temperature and Humidity Control:
    • The HVAC system must maintain constant temperature and humidity within defined ranges:
      • Temperature: Between 18°C and 24°C for most cleanroom applications.
      • Humidity: Typically, 30%–60% relative humidity to prevent static electricity buildup and ensure optimal process conditions.
    • Humidity Control: Humidifiers and dehumidifiers should be integrated into the HVAC system to ensure that relative humidity stays within the specified range.
  • Ventilation Zones: The HVAC system should support multiple cleanroom zones with independent ventilation and pressure control. This ensures that contamination risks from less-critical areas are minimized when entering critical zones (e.g., sterile zones).

Commissioning of HVAC Systems

Lighting:

  • Lighting Type:
    • LED Lights: Use LED lighting, as it offers high energy efficiency, low heat output, and long-lasting performance. The LED lights should be non-glare to ensure proper visibility and reduce particle disturbances in the cleanroom.
  • Illumination Levels:
    • Lighting levels should be appropriate for the tasks performed in the cleanroom while maintaining cleanroom standards:
      • ISO Class 5 or sterile environments: Typically, 1000–1500 lux.
      • ISO Class 7 or 8 environments: Typically, 500–1000 lux.
    • The lighting should provide even illumination across the entire cleanroom and meet task-specific requirements (e.g., assembly, inspection, or pharmaceutical manufacturing).
  • Light Fixtures:
    • Fixtures should be flush-mounted and designed for easy cleaning, with sealed joints to prevent contamination buildup.
    • Antimicrobial Coatings: Consider using light fixtures with antimicrobial coatings to minimize contamination risks further.

Electrical Systems:

  • Power Requirements:
    • The cleanroom must have a dedicated electrical supply to ensure that critical systems (e.g., HVAC, lighting, and monitoring systems) are not interrupted.
    • The main electrical panel should include dedicated circuits for HVAC systems, lighting, and critical equipment.
    • Power outlets should be grounded and appropriate for cleanroom conditions, with protection from electrical surges or interruptions. The wiring and outlets should comply with local electrical codes and cleanroom standards.
  • Emergency Backup Power:
    • Critical systems, including HVAC, lighting, and monitoring systems, should have an uninterruptible power supply (UPS) to ensure that operations are not disrupted during power outages.
    • An emergency backup generator should be available to supply power to essential systems during extended power failures.
  • Electrical Safety:
    • Ground Fault Circuit Interrupters (GFCI) should be used to prevent electrical shocks in wet or humid environments.
    • All electrical installations should include safety features such as circuit breakers and fuses to prevent overload and short circuits.
  • Redundancy and Monitoring:
    • Ensure critical systems, such as HVAC, are equipped with redundant power supplies (e.g., backup power circuits) to maintain continuous operation.
    • Consider integrating automatic monitoring of electrical systems to detect faults and automatically switch to backup systems when needed.

Plumbing and Waste Disposal:

  • Water Systems:
    • Cleanroom Water Systems: The cleanroom water supply should meet purity standards, such as pure or ultrapure water, for processes requiring high cleanliness levels (e.g., pharmaceutical manufacturing).
    • Water systems should include filtration and disinfection stages to ensure the water meets cleanroom specifications.
    • Water Treatment: The system should include appropriate water treatment technologies (e.g., reverse osmosis, deionization, UV sterilization) to maintain water quality.
  • Plumbing Requirements:
    • Plumbing must be designed to prevent contamination. Use smooth, non-porous pipes and fittings to seal all connections to prevent leaks and contamination.
    • Any water dispensers or sinks within the cleanroom must be designed for easy cleaning and sterilization.
  • Waste Disposal Systems:
    • Wastewater should be filtered and treated to prevent contamination from leaving the cleanroom.
    • Design waste disposal systems that ensure the safe removal of non-hazardous and hazardous waste (e.g., biological, chemical, and pharmaceutical waste) in compliance with regulatory requirements.
    • Install separate waste streams for cleanroom and hazardous materials to prevent cross-contamination.
  • Waste Collection and Handling:
    • Waste collection bins within the cleanroom should be sealed, easy to clean, and made of non-porous, anti-static materials.
    • Consider integrating automated waste removal systems to reduce the risk of contamination by human interaction.
  • Plumbing Safety and Monitoring:
    • Install backflow preventers to avoid contamination of the cleanroom water supply from external sources.
    • Consider implementing automated monitoring systems for water quality (e.g., pH, conductivity, particulate contamination)

6. Monitoring and Control Systems

Environmental Monitoring:

Environmental monitoring is critical for ensuring the cleanroom maintains the necessary conditions for sensitive processes and product integrity. The monitoring system should track key environmental parameters in real time and notify operators of deviations.

  • Key Parameters to Monitor:
    • Temperature: Continuous temperature monitoring is required to ensure it remains within a specified range (e.g., 18°C to 24°C). Fluctuations outside this range can affect the cleanliness and performance of the cleanroom environment.
    • Humidity: The relative humidity should be monitored and maintained between 30% and 60%. Variations outside this range can cause static electricity buildup, contamination, or process inefficiencies.
    • Particle Count: The particle count is a critical parameter for cleanroom classifications. The system should monitor airborne particle concentrations based on ISO classifications (e.g., 0.3 microns or smaller). Particle counters should be integrated with the HVAC system to measure air quality.
    • Air Pressure Differential: The pressure differential between the cleanroom and adjacent spaces should be monitored continuously to ensure the cleanroom maintains positive pressure, preventing contamination from less-clean areas. A differential of at least 10 Pa is typically required.
  • Monitoring Frequency:
    • Real-Time Monitoring: Parameters should be continuously monitored in real time to detect deviations immediately. Data should be updated at least every minute to provide up-to-date environmental conditions.
    • Periodic Verification: In addition to real-time monitoring, periodic manual verification (e.g., once every 24 hours) should be conducted to cross-check automated readings and ensure system accuracy.
  • Acceptable Limits for Deviation:
    • Temperature: Deviation of no more than ±2°C from the setpoint.
    • Humidity: Deviation of no more than ±5% relative humidity.
    • Particle Count: Particle levels must not exceed the specified count for the cleanroom classification (e.g., ISO Class 5 must not exceed 3,520 particles per cubic meter for 0.5 microns or larger particles).
    • Air Pressure: The pressure differential should be maintained at a minimum of 10 Pa.

Contamination Control:

Controlling contamination is essential to maintaining cleanroom integrity. Specific systems for particle counting and microbial monitoring should be in place.

  • Particle Counting Systems:
    • Particle Counters: Use light-scattering particle counters that measure particles at specific sizes (typically 0.3 microns, but counters for other sizes may be used as required). These should be calibrated to meet the cleanliness level (e.g., ISO Class 5, 7, 8) and integrated with HVAC systems to monitor particulate concentrations in real-time.
    • Automatic Monitoring: Particle counters should be connected to an automated monitoring system to provide continuous data logging and alert systems for real-time tracking of contamination levels.
  • Microbial Monitoring Systems:
    • Microbial Air Sampling: Measure airborne microbial contamination using active air sampling systems, such as Andersen samplers or impaction samplers. Sampling should be performed at defined intervals (e.g., every 1–2 hours in critical areas like sterile zones).
    • Surface Sampling: Use contact plates or swabs for periodic surface microbiological testing to detect contamination from equipment, floors, walls, or other surfaces.
    • Microbial Growth Media: Using agar plates or biological indicators for microbial colony growth testing. Ensure that the growth media meets regulatory guidelines and provides accurate results.
  • Additional Contamination Controls:
    • Install HEPA or ULPA filters within the HVAC system to continuously filter particles and microorganisms from the air. The integrity of these filters should be periodically tested.

Data Logging and Alarm Systems:

An effective data logging system is crucial for tracking cleanroom conditions, ensuring compliance, and alerting personnel when environmental parameters are out of specification.

  • Data Logging Requirements:
    • The environmental monitoring system should continuously log data from the various monitoring sensors (temperature, humidity, particle counts, air pressure) into a centralized database.
    • Data should be logged with a frequency of at least every minute for real-time accuracy.
    • Historical data should be stored for at least 12 months to comply with regulatory requirements (e.g., GMP or FDA regulations).
  • Alarm Systems:
    • Threshold Alarms: The system should be configured to trigger alarms if any monitored parameter (e.g., temperature, humidity, particle count, or air pressure) falls outside the defined acceptable limits.
    • Alarm Types: Alarms should include visual indicators (e.g., flashing lights or display messages) and audible alerts (e.g., alarms or sirens) to notify personnel immediately.
    • Escalation Protocol: The system should include an escalation protocol where alarms are forwarded to higher-level supervisory personnel if the issue is not addressed within a specified time (e.g., 10 minutes).
    • Remote Monitoring: Ensure critical data can be accessed remotely through a web-based platform or mobile application to allow real-time monitoring and prompt response to any issues.

Cleanroom Status Indicators:

Clear visual and auditory signals are necessary for cleanroom personnel to ensure they work within specifications and maintain cleanroom integrity.

  • Visual Indicators:
    • Green/Red Lights: Use traffic lights or indicator lamps near entry/exit points or key cleanroom zones. Green lights indicate that the cleanroom operates within the required parameters, and red lights indicate that conditions are outside acceptable specifications.
    • Display Panels: Digital or analog status display panels should show the current environmental parameters (e.g., temperature, humidity, particle count) for transparency and immediate awareness.
  • Audible Alarms:
    • In addition to visual indicators, audible alarms (e.g., sirens, bells) should be triggered when any parameter exceeds the defined limits, alerting personnel to take corrective actions.
  • Status Monitoring Systems:
    • Integrated Status Display: The monitoring system should provide an integrated central status display in the cleanroom area, displaying live updates on the environmental conditions and any deviations from set parameters

7. Safety and Emergency Requirements

Emergency Procedures:

Emergencies in the cleanroom environment can occur due to equipment failure, power loss, or disruptions in airflow. Clear and structured procedures must be established to mitigate risks and restore normal operations.

  • Equipment Failure:
    • Procedure for Identifying Failure:
      • Establish an alarm system for equipment failures, such as malfunctioning HVAC systems, particle counters, or temperature control devices.
      • Perform regular preventive maintenance and system checks to reduce the likelihood of failure.
    • Corrective Action:
      • If equipment fails, the cleanroom manager or supervisor should be notified immediately.
      • Backup Systems (e.g., generators or alternative equipment) should be in place to minimize disruption.
      • In case of critical equipment failure (e.g., HVAC or temperature control systems), the cleanroom should be evacuated until it is safe to return.
    • Recovery Plan:
      • Define the time frame for restoring normal operations and ensure proper documentation of any actions taken to resolve the issue.
      • Post-Incident Review: The incident should be reviewed to identify the root cause, assess the response, and prevent future occurrences.
  • Power Loss:
    • Backup Power Systems:
      • To maintain critical operations like HVAC, lighting, and monitoring systems, a backup generator or an uninterruptible power supply (UPS) must be in place.
      • Ensure backup power systems are tested regularly to confirm their reliability during power outages.
    • Power Loss Procedure:
      • In the event of a power loss, the emergency system should activate automatically to maintain temperature, airflow, and pressure controls.
      • Personnel evacuation may be required if power loss threatens cleanroom conditions (e.g., contamination risk or product integrity concerns).
  • Airflow Disruption:
    • Airflow Disruption Procedure:
      • Immediate activation of backup HVAC systems to restore airflow in case of HVAC failure.
      • In case of extended disruption, consider evacuating personnel from the cleanroom.
      • Record the incident for review, including the duration and reasons for disruption.

Fire Safety:

Fire safety is critical to cleanroom design, especially since some materials used in cleanroom construction (e.g., plastics or chemical substances) may be flammable or hazardous.

  • Fire Suppression System:
    • Fire Suppression Method:
      • The cleanroom must be equipped with a suitable fire suppression system. Depending on the cleanroom classification and the materials in use, options could include:
        • Sprinkler Systems for general fire suppression in less sensitive areas.
        • Inert Gas Systems (e.g., CO2 or FM-200) for areas where water-based systems may be inappropriate (e.g., areas containing electrical equipment or sensitive materials).
    • Fire Detection and Alarm Systems:
      • Integrate smoke detectors, heat detectors, and manual pull stations connected to an automated alarm system to notify personnel immediately.
    • Evacuation Plan:
      • Ensure clear exit routes and procedures for personnel evacuation in case of fire. This includes well-marked exits and emergency exits.
      • Provide fire exits that are easily accessible and not obstructed by equipment or materials.
    • Fire Safety Drills:
      • Conduct regular fire drills to ensure all personnel are trained in evacuation procedures and familiar with emergency exits.

Hazardous Materials:

Handling hazardous materials, such as flammable, toxic, or corrosive substances, within a cleanroom requires strict procedures to minimize risks to personnel, products, and the environment.

  • Hazardous Materials Handling:
    • Material Classification:
      • Identify and clearly label all hazardous materials in the cleanroom (e.g., flammable chemicals, biological agents, or corrosive substances).
    • Containment and Storage:
      • Store hazardous materials in dedicated, sealed containers designed for the specific chemical properties of the material (e.g., fireproof cabinets for flammable materials).
      • Ensure ventilation systems are appropriate to prevent the buildup of toxic fumes or gases in the cleanroom.
    • Personal Protective Equipment (PPE):
      • Define the required PPE for handling hazardous materials, including gloves, goggles, lab coats, and respirators.
    • Spill Containment and Cleanup:
      • Provide spill containment kits for each cleanroom area, with clear procedures for containing and cleaning up hazardous spills.
      • Use specialized disposal containers for hazardous waste, such as chemical or biohazard bags.
    • Material Safety Data Sheets (MSDS):
      • Ensure that MSDS for all hazardous materials are readily accessible to cleanroom personnel for reference.

Access Control and Security:

Restricting access to the cleanroom is critical to maintaining its controlled environment and preventing contamination or unauthorized access to sensitive areas.

  • Access Control Systems:
    • Physical Barriers:
      • Install secure entry points with physical barriers (e.g., doors, airlocks) to control the flow of personnel in and out of the cleanroom.
      • Use interlocking doors (e.g., airlocks) to maintain cleanroom pressure and cleanliness when personnel enter or exit.
    • Electronic Access Control:
      • Utilize electronic badge systems or smart cards for authorized personnel access. Each badge should be programmable to restrict access to designated areas.
      • Keep a record of all personnel entering and exiting the cleanroom, ensuring audit trails are available for compliance.
    • Visitor Management:
      • Non-authorized personnel (e.g., visitors and contractors) must always be escorted in cleanroom areas. Issue visitor badges that limit access to specific zones.
      • Define visitor gowning procedures and requirements to prevent contamination.
  • Personnel Gowning and De-gowning:
    • Gowning Procedures:
      • Define a strict gowning procedure that includes cleanroom suits, gloves, masks, and hair coverings. Employees must gown in designated gowning areas before entering the cleanroom.
    • De-gowning Procedures:
      • Create a de-gowning area where personnel can safely remove their protective gear after leaving the cleanroom, minimizing the risk of contamination from external environments.
  • Surveillance and Security:
    • CCTV and Monitoring Systems:
      • Install CCTV cameras at key entry points and within the cleanroom to monitor access and ensure compliance with cleanroom protocols.
      • Ensure security measures to prevent unauthorized access, such as biometric scanners or access logs

8. Maintenance and Validation

Cleaning and Maintenance Procedures:

Maintaining a cleanroom environment is essential for ensuring product quality, preventing contamination, and complying with regulatory requirements. Detailed cleaning and maintenance protocols should be established to ensure the room remains within the required cleanliness classification.

  • Routine Cleaning Procedures:
    • Cleaning Frequency:
      • Daily Cleaning: Clean high-touch areas, floors, walls, and surfaces that may accumulate particulate contamination daily.
      • Weekly Cleaning: Clean and disinfect the air handling units, exhaust vents, and lighting fixtures. Ensure all surfaces in the gowning area and storage areas are cleaned weekly.
      • Monthly Cleaning: Perform deep cleaning activities, such as cleaning HVAC ducts, ceiling grids, and HEPA filters.
    • Cleaning Agents:
      • Approved Cleaning Agents: Use non-abrasive and non-volatile cleaning agents that do not leave residues. Commonly used agents include isopropyl alcohol (IPA) and quaternary ammonium compounds. Ensure all cleaning agents are compatible with cleanroom materials and do not affect product integrity.
      • Disinfectants: For cleanrooms used in pharmaceutical or biotechnology sectors, specify disinfectants that meet regulatory requirements and are effective against microbial contaminants.
    • Cleaning Methods:
      • Wiping: Use lint-free wipes or cloths to wipe down surfaces to prevent fibre shedding and particle generation.
      • Vacuuming: Employ HEPA-filtered vacuums to clean floors and other surfaces and reduce particle accumulation.
      • Floor Scrubbing: To maintain a consistent level of cleanliness in large cleanroom floor areas, use automatic floor scrubbers with HEPA filters.
  • Maintenance Procedures:
    • Routine Equipment Checks:
      • Perform scheduled maintenance on cleanroom equipment (e.g., HVAC systems, air handling units, particle counters, and lighting systems).
      • Regularly check and replace air filters (HEPA and ULPA) to maintain airflow and filtration efficiency.
    • Calibration and Performance Testing:
      • Calibrate temperature, humidity, and pressure sensors regularly to ensure accurate readings.
      • Verify that the HVAC system operates within specifications, ensuring consistent airflow and temperature control.
    • Surface Inspections:
      • Inspect surfaces for wear, cracks, or potential contamination traps and repair any damage to prevent contamination.

Validation and Commissioning:

Cleanroom validation and commissioning are critical to ensuring that the cleanroom environment meets its intended specifications and complies with regulatory requirements.

  • Cleanroom Validation Protocols:
    • Airflow Testing:
      • Airflow velocity and direction should be measured using anemometers and velometers to ensure that airflow meets cleanroom classification requirements. Verify that airflow is unidirectional (for critical areas) or turbulent (for general areas), as specified by the cleanroom class.
    • Pressure Differential:
      • Pressure testing should be conducted to ensure that pressure differentials are maintained between adjacent cleanroom areas, as required by the design (e.g., a minimum of 10 Pa for adjacent rooms).
      • Use differential pressure gauges to monitor pressure levels and ensure air flows from cleaner to less clean areas.
    • Temperature and Humidity Testing:
      • Validate that the temperature and humidity levels are consistent with design specifications and meet industry requirements (e.g., temperature between 18-24°C, humidity between 30-60%).
      • During the commissioning phase, data loggers or real-time monitoring systems should be employed to track temperature and humidity over a set period.
    • Particulate Contamination Levels:
      • Particle counters should be used to measure particulate contamination in the cleanroom air. These readings should align with the cleanroom class’s ISO 14644-1 classification requirements (e.g., ISO Class 5, Class 7).
      • Verify that particle counts meet the required limits for the cleanroom classification in critical areas.
    • Microbial Monitoring:
      • Conduct microbial sampling (e.g., surface swabs, air sampling) to verify that microbial levels are within acceptable limits, especially for pharmaceutical or biotech cleanrooms.
  • Commissioning Documents:
    • After the commissioning process, document all testing results, including any deviations and corrective actions, in a validation report.
    • Maintain test certificates for all equipment, such as HVAC systems, HEPA filters, and air monitoring devices, to confirm that it was tested and is operating to specifications.

Ongoing Qualification:

Ongoing qualification ensures that the cleanroom continues to perform as expected and remains compliant with applicable regulatory standards throughout its operational life.

  • Requalification Procedures:
    • Periodic Requalification:
      • The cleanroom should be requalified at regular intervals (e.g., annually or biannually) or whenever significant changes are made to the facility (e.g., equipment installation, facility modifications).
      • The requalification process should include checks of airflow, pressure differentials, temperature, humidity, particle counts, and microbial levels, as well as routine maintenance of equipment.
    • Qualification of New Equipment:
      • When new equipment is introduced into the cleanroom (e.g., new HVAC units, particle counters, or lighting systems), ensure that the equipment is validated for cleanroom use and does not compromise the cleanroom’s performance.
      • Test and document the impact of any new equipment on the cleanroom environment before it is used regularly.
  • Revalidation Protocols:
    • Revalidation after Major Events:
      • If significant events occur (e.g., power failure, system malfunction, or major renovations), the cleanroom must be revalidated to ensure it meets all specifications.
    • Continuous Monitoring:
      • Ongoing qualification involves continuous or periodic environmental monitoring (e.g., particle counts, temperature, and humidity) with automated alarms and data logging.
      • Implement preventive maintenance programs for key equipment (e.g., HVAC systems, particle counters, and HEPA filters) to ensure they remain within specification

9. Documentation and Record-Keeping

Standard Operating Procedures (SOPs):

Standard Operating Procedures (SOPs) are essential for maintaining consistent operations, ensuring compliance, and mitigating risks in cleanroom environments. They define how processes should be executed to maintain cleanroom standards, minimize contamination, and ensure safety.

  • SOPs for Cleanroom Operations:
    • Cleanroom Entry and Exit Procedures:
      • Establish personnel entry and exit procedures, including gowning and degowning processes, to minimize contamination risks.
      • Ensure that entry and exit points are designated, personnel undergo proper sanitization and wear appropriate cleanroom attire.
    • Environmental Monitoring:
      • Create SOPs to monitor key environmental parameters such as temperature, humidity, air pressure, and particulate counts.
      • Include the methods for routine testing, frequencies, and acceptable deviation limits.
    • Airflow and HVAC Monitoring:
      • Develop SOPs for maintaining and monitoring the HVAC system to ensure it provides airflow, filtration, and temperature/humidity control.
      • Define protocols for regular checks, maintenance, and troubleshooting.
    • Cleaning Procedures:
      • Provide detailed cleaning SOPs, including daily, weekly, and monthly cleaning tasks, approved cleaning agents, and techniques to prevent cross-contamination.
      • Specify how to clean and disinfect high-touch surfaces, equipment, and tools.
    • Handling and Disposal of Waste:
      • Outline procedures for handling hazardous or non-hazardous waste materials, including disposal methods that comply with regulations.
      • Include methods for segregating waste based on type (e.g., biological, chemical, or general waste).
    • Emergency Procedures:
      • Develop SOPs for dealing with emergencies such as power failure, equipment malfunction, contamination incidents, or accidents within the cleanroom.
      • Include protocols for cleaning and sanitizing following a contamination event and notifying the appropriate personnel.
    • Personnel Safety:
      • Define SOPs related to personnel safety, including training programs, proper gowning techniques, personal protective equipment (PPE), and health and safety measures.
  • SOPs for Maintenance and Calibration:
    • Equipment Maintenance:
      • To ensure they remain functional and compliant, SOPs should be developed to maintain cleanroom equipment, such as HVAC systems, particle counters, and lighting systems.
    • Calibration Procedures:
      • Establish SOPs for calibrating monitoring equipment (e.g., thermometers, pressure gauges, particle counters) to ensure accurate reading and reliability.

Record-Keeping:

Accurate and comprehensive record-keeping is crucial for compliance, traceability, and audits. The records generated should be maintained for the required retention period and be readily accessible for inspection.

  • Types of Records to Be Maintained:
    • Environmental Monitoring Logs:
      • Maintain logs that capture real-time data for temperature, humidity, particle counts, and pressure differentials. These logs should include dates, times, and deviations from set parameters.
      • Keep records of alarm triggers and corrective actions taken.
    • Maintenance Logs:
      • Document routine and emergency maintenance activities for all cleanroom equipment, such as HVAC systems, particle counters, and monitoring devices.
      • Include details on equipment inspections, repairs, replacements, and calibrations.
    • Cleaning and Disinfection Logs:
      • Maintain records of cleaning activities, including who performed the cleaning, what was cleaned, and the cleaning agents used.
      • Track cleaning frequencies (daily, weekly, monthly) and ensure compliance with the cleaning SOPs.
    • Validation and Commissioning Reports:
      • Keep detailed records of all cleanroom validation and commissioning activities, including test protocols, results, deviations, corrective actions, and final validation reports.
      • These should include the validation certificates for all systems (e.g., HVAC, monitoring equipment).
    • Training Records:
      • Maintain records of personnel training and certifications for cleanroom operations, maintenance, and safety.
      • Ensure these records are up to date and accessible for regulatory inspections.
    • Audit Logs:
      • Keep detailed logs of internal audits, external audits, and regulatory inspections.
      • Include audit findings, corrective actions taken, and any follow-up verification.
  • Retention Period:
    • Ensure records are stored for the required period per regulatory requirements (e.g., 3-5 years, depending on local or international regulations) and easily retrievable.

Compliance Documentation:

Compliance documentation ensures that the cleanroom adheres to applicable regulatory and industry standards. It serves as evidence of conformity and readiness for inspections.

  • Audit Trails:
    • Ensure that all electronic records (e.g., environmental monitoring systems, maintenance records) have audit trails that log the identity of the individual making changes, the date and time of changes, and a reason for the change.
    • Audit trails should be secure, tamper-proof, and compliant with data integrity regulations (e.g., 21 CFR Part 11, if applicable).
  • Certificates of Compliance:
    • Obtain certificates from suppliers and manufacturers for the cleanroom equipment, including:
      • Calibration Certificates: These are for all monitoring devices, such as particle counters, temperature/humidity sensors, and pressure gauges.
      • Performance Certificates: For HVAC systems, HEPA filters, and other critical cleanroom systems.
      • Compliance Certificates: Ensure all construction materials and cleaning agents comply with relevant industry standards (e.g., ISO 14644-1, GMP).
  • Validation Certificates:
    • Maintain validation certificates for the cleanroom’s HVAC systems, airflow dynamics, temperature, humidity, and particulate contamination levels.
    • These certificates should be based on accepted standards and regulatory requirements, such as those specified by ISO 14644-1 and cGMP for pharmaceutical environments.
  • Regulatory Compliance Reports:
    • Keep records of compliance reports related to FDA, Health Canada, or other relevant health authorities’ inspections and certifications.
    • Ensure that any non-conformities are addressed, documented, and resolved following regulatory standards

10. Timeline and Budget

  • Project Timeline:
    • Provide estimated project timelines for design, construction, validation, and commissioning.
  • Budget:
    • Include budget estimates for cleanroom construction, equipment, and ongoing maintenance costs.

Conclusion

The User Requirement Specification (URS) for a cleanroom is essential for defining the key operational, environmental, safety, and compliance requirements the cleanroom must meet. It serves as the foundation for the facility’s design, construction, and validation, ensuring it is built to industry standards and capable of maintaining the required environment for sensitive operations.

Contact GxP Cellators Consultants for Cleanroom Documentation and Support

For expert assistance with your cleanroom documentation and full lifecycle support—from project initiation to go-live of your cleanroom operations—contact GxP Cellators. Our team is highly skilled in overseeing Commissioning, Qualification, and Validation (CQV) operations for greenfield and brownfield projects.

Contact Information:

  • Email:
  • Website: www.gxpcellators.com

Let our experienced consultants guide you through every stage of your cleanroom project to ensure compliance, efficiency, and successful operations.

 


Leave a Reply

This site uses Akismet to reduce spam. Learn how your comment data is processed.


Our Presence



Saskatchewan, Canada

Calgary, Canada

Toronto, Canada

North Carolina, USA

Frankfurt, Germany


Indiana, USA

SSL site seal - click to verify

Get in Touch



+1 (306) 715 -9460


Saskatchewan, Canada

https://www.gxpcellators.com


wpChatIcon
wpChatIcon

You cannot copy content of this page

Verified by MonsterInsights